Mar. 2023 | Apr. 2020 | |
Pump Station 1 | SWL 6.95 MTRS PWL 12.8 MTRS | SWL 6.95 MTRS PWL 12 MTRS |
Pump Station 2 | SWL 13 MTRS PWL 19.8 MTRS | SWL 13 MTRS PWL 21 MTRS |
Pump Station 3 | SWL 8 MTRS PWL 13 MTRS | SWL 7.50 MTRS PWL 19.50 MTRS |
Pump Station 4 | SWL 14 MTRS PWL 20.40 MTRS | SWL 13.8 MTRS PWL 20 MTRS |
Pump Station 5 | SWL 6 MTRS PWL 16.5 MTRS | SWL 6 MTRS PWL 16 MTRS |
Pump Station 6 | SWL 4.60 MTRS PWL 6.20 MTRS | SWL 4.60 MTRS PWL 7 MTRS |


Pump Station No. 1 – Craser, Polanco, Z.N.
WELL:
Bore Hole – 16 inches
Depth – 72 mtrs
Casing – 10 inches Spiral Welded Steel
Casing Perforation – Stainless Steel Wire Wound Screen
Well Capacity – 32 LPS
Static Water Level – 5 mtrs
PUMP:
-> DYNA FlO
No. of Bowls – 4
Discharge – 230 GPM
Diameter – 3 inches
Effeciency –
Setting – 18 mtrs
MOTOR
-> FRANKLIN ELECTRIC MOTOR, 15 HP
230 volts
60 H2
DATE OF OPERATION: DECEMBER 22, 1995
OPERATION HOURS/DAY = 16 Hrs.
PRODUCTION IN CU.M/DAY = 1,016 cu.m
MOTOR CONTROLLER:
20 HP AUTOTRANSFORMER
->230 VOLTS, 3 PHASE
GRAVEL PACK LEVEL: 15 MTRS


PUMP STATION 2 – Conacon, Polanco, Z.N.
WELL:
Bore Hole – 16 inches
Depth – 80 mtrs
Casing – 8 inches Spiral Welded Steel
Casing Perforation – Stainless Steel Wire Wound Screen
Well Capacity – 15 LPS
Static Water Level – 11.65 mtrs
PWL : 20.55
PUMP:
->SHAKTI PUMP
No. of Bowls – 15
Discharge – 15 LPS
Diameter – 5 inches
Effeciency – 64%
Setting – 31 mtrs
MOTOR:
-> FRANKLIN ELECTRIC MOTOR 15 HP
230 VOLTS
60 HZ
DATE OF OPERATION: December 1, 2008
OPERATING HOURS/DAY = 17 HOURS
PRODUCTION IN CU.M/DAY = 694.80 CU.M
MOTOR CONTROLLER:
15 HP AUTOTRANSFORMER
->230 VOLTS, 3 PHASE
GRAVEL BACK LEVEL : 15.60 MTRS


PUMP STATION 3 – Sinanga, Anastacio, Polanco, Z.N.
WELL:
Bore Hole – 16 inches
Depth – 102 mtrs
Casing – 8 inches Spiral Welded Steel
Casing Perforation – Stainless Steel Wire Wound Screen
Well Capacity – 20 LPS
Static Water Level – 7 mtrs
PUMP:
->DYNA-FLO PUMP
No. of Bowls – 4
Discharge – 20 LPS
Diameter – 4 inches
Setting – 23 mtrs
MOTOR:
-> FRANKLIN ELECTRIC MOTOR 20 HP
230 VOLTS
60 HZ
DATE OF OPERATION: December 6, 2008
OPERATING HOURS/DAY = 2 HOURS
PRODUCTION IN CU.M/DAY = 108 CU.M
MOTOR CONTROLLER:
20 HP AUTOTRANSFORMER
->230 VOLTS, 3 PHASE
GRAVEL BACK LEVEL : 16.50 MTRS




PUMP STATION 5 – Sinanga, Obay, Polanco, Z.N.
WELL:
Bore Hole – 16 inches
Depth –
Casing – 8 inches Spiral Welded Steel
Casing Perforation – Stainless Steel Wire Wound Screen
Well Capacity –
Static Water Level – 7 mtrs
PUMP:
No. of Bowls – 6
Discharge – 15 LPS
Efficiency –
Setting – 27 mtrs
MOTOR:
-> FRANKLIN ELECTRIC MOTOR 25 HP
230 VOLTS
60 HZ
DATE OF OPERATION: February 2020
OPERATING HOURS/DAY =
PRODUCTION IN CU.M/DAY =
MOTOR CONTROLLER:
25 HP AUTOTRANSFORMER
->230 VOLTS, 3 PHASE
GRAVEL PACK LEVEL : 14.50 MTRS


PUMP STATION 6 – Maralag, Guinles, Polanco, Z.N.
WELL:
Bore Hole – 16 inches
Depth –
Casing – 8 inches Spiral Welded Steel
Casing Perforation – Stainless Steel Wire Wound Screen
Well Capacity –
Static Water Level –
PUMP:
No. of Bowls – 6
Discharge – 18 LPS
Efficiency –
Setting –
MOTOR:
-> FRANKLIN ELECTRIC MOTOR 15 HP
230 VOLTS
60 HZ
DATE OF OPERATION: September 2020
OPERATING HOURS/DAY = 10 Hrs
PRODUCTION IN CU.M/DAY = 187 cu.m
MOTOR CONTROLLER:
15 HP VFD MOTOR CONTROLLER
->230 VOLTS, 3 PHASE
GRAVEL PACK LEVEL : 14.30 MTRS